3.7 Schedule 2 – Exclusion zones
3.7.1 Part 1 – exclusion zones for exposed parts for untrained persons
3.7.2 Part 2 – exclusion zones for exposed parts for authorised and instructed persons
3.7.3 Part 3 – exclusion zones for low voltage overhead for untrained persons
3.7.4 Part 4 – exclusion zones for low voltage overhead for authorised and instructed persons
3.7.5 Part 5 – exclusion zones for high voltage overhead for untrained persons
3.7.6 Part 6 – exclusion zones for high voltage overhead for authorised and instructed persons
3.7.1 Part 1 – exclusion zones for exposed parts for untrained persons and for operating plant and vehicles operated by untrained persons
|
Nominal phase to phase voltage of exposed part |
Untrained person for the exposed part (mm) |
Operating plant operated by untrained person for the exposed part (mm) |
Vehicle operated by untrained person for the exposed part (mm) |
|---|---|---|---|
|
Low voltage (with consultation with person in control of exposed part) |
1 000 |
3 000 |
600 |
|
Low voltage (without consultation with person in control of exposed part) |
3 000 |
3 000 |
600 |
|
Above low voltage, up to 33 kV (with consultation with person in control of exposed part) |
2 000 |
3 000 |
900 |
|
Above low voltage, up to 33 kV (without consultation with person in control of exposed part) |
3 000 |
3 000 |
900 |
|
Above 33 kV up to 50 kV |
3 000 |
3 000 |
2 100 |
|
Above 50 kV up to 66 kV |
3 000 |
3 000 |
2 100 |
|
Above 66 kV up to 110 kV |
3 000 |
3 000 |
2 100 |
|
Above 110 kV up to 132 kV |
3 000 |
3 000 |
2 100 |
|
Above 132 kV up to 220 kV |
4 500 |
6 000 |
2 900 |
|
Above 220 kV up to 275 kV |
5 000 |
6 000 |
2 900 |
|
Above 275 kV up to 330 kV |
6 000 |
6 000 |
3 400 |
|
Above 330 kV up to 440 kV |
6 000 |
8 000 |
4 400 |
|
Above 400 kV up to 500 kV |
6 000 |
8 000 |
4 400 |
|
Nominal pole to earth dc voltage of exposed part |
|||
|
+/- 25 kV |
3 000 |
3 000 |
900 |
|
+/- 85 kV |
3 000 |
3 000 |
2 100 |
|
+/- 150 kV |
3 000 |
3 000 |
2 100 |
|
+/- 270 kV |
4 500 |
6 000 |
2 900 |
|
+/- 350 kV |
5 000 |
6 000 |
2 900 |
|
+/- 400 kV |
6 000 |
6 000 |
3 400 |
3.7.2 Part 2 – exclusion zones for exposed parts for authorised and instructed persons and for operating plant and vehicles operated by authorised or instructed persons
|
Nominal phase to phase voltage of exposed part |
Authorised person or instructed person for the exposed part (mm) |
Operating plant operated by authorised person or instructed person for the exposed part, with safety observer or another safe system of work (mm) |
Vehicle operated by authorise person or instructed person for the exposed part (mm) |
|---|---|---|---|
|
Low voltage (with consultation with person in control of exposed part) |
(No exclusion zone prescribed) |
1 000 |
600 |
|
Low voltage (without consultation with person in control of exposed part) |
(No exclusion zone prescribed) |
1 000 |
600 |
|
Above low voltage, up to 33 kV (with consultation with person in control of exposed part) |
700 |
1 200 |
700 |
|
Above low voltage, up to 33 kV (without consultation with person in control of exposed part) |
700 |
1 200 |
700 |
|
Above 33 kV up to 50 kV |
750 |
1 300 |
750 |
|
Above 50 kV up to 66 kV |
1 000 |
1 400 |
1 000 |
|
Above 66 kV up to 110 kV |
1 000 |
1 400 |
1 000 |
|
Above 110 kV up to 132 kV |
1 200 |
1 800 |
1 200 |
|
Above 132 kV up to 220 kV |
1 800 |
2 400 |
1 800 |
|
Above 220 kV up to 275 kV |
2 300 |
3 000 |
2 300 |
|
Above 275 kV up to 330 kV |
3 000 |
3 700 |
3 000 |
|
Above 330 kV up to 400 kV |
3 300 |
4 000 |
3 300 |
|
Above 400 kV up to 500 kV |
3 900 |
4 600 |
3 900 |
|
Nominal pole to earth dc voltage of exposed part |
|||
|
+/- 25 kV |
700 |
1 200 |
700 |
|
+/- 85 kV |
1 000 |
1 800 |
1 000 |
|
+/- 150 kV |
1 200 |
1 800 |
1 200 |
|
+/- 270 kV |
1 800 |
2 400 |
1 800 |
|
+/- 350 kV |
2 500 |
3 200 |
2 500 |
|
+/- 400 kV |
2 900 |
3 600 |
2 900 |
3.7.3 Part 3 – exclusion zones for low voltage overhead insulated electric line for untrained persons and for operating plant or vehicles operated by untrained persons
|
Low voltage overhead insulated electric line |
Untrained person (mm) |
Operating plant operated by untrained person for the electric line (mm) |
Vehicle operated by untrained person for the electric line (mm) |
|---|---|---|---|
|
With consultation with, and insulation verified by, an authorised person for the electric line |
(No exclusion zone prescribed) |
1 000 |
300 |
|
Without consultation with, and without insulation verified by, an authorised person for the electric line |
3 000 |
3 000 |
600 |
3.7.4 Part 4 – exclusion zones for low voltage overhead insulated electric line for authorised or instructed persons and for operating plant or vehicles operated by authorised or instructed persons
|
Low voltage overhead insulated electric line |
Authorised person or instructed person for the electric line (mm) |
Operating plant operated by authorised person or instructed person for the electric line, with safety observer or another safe system of work (mm) |
Vehicle operated by authorised person or instructed person for the electric line (mm) |
|---|---|---|---|
|
With consultation with, and insulation verified by, an authorised person for the electric line |
(No exclusion zone prescribed) |
(No exclusion zone prescribed) |
(No exclusion zone prescribed) |
|
Without consultation with, and without insulation verified by, an authorised person for the electric line |
(No exclusion zone prescribed) |
(No exclusion zone prescribed) |
600 |
3.7.5 Part 5 – exclusion zones for high voltage overhead insulated electric line for untrained persons and for operating plant or vehicles operated by untrained persons
|
Nominal phase to phase voltage of high voltage overhead insulated electric line |
Untrained person for the electric line (mm) |
Operating plant operated by untrained person for the electric line (mm) |
Vehicle operated by untrained person for the electric line (mm) |
|---|---|---|---|
|
Above low voltage, up to 33 kV (with consultation with person in control of electric line) |
2 000 |
3 000 |
900 |
|
Above low voltage, up to 33 kV (without consultation with person in control of electric line) |
3 000 |
3 000 |
900 |
|
Above 33 kV up to 50 kV |
3 000 |
3 000 |
2 100 |
|
Above 50 kV up to 66 kV |
3 000 |
3 000 |
2 100 |
|
Nominal pole to earth dc voltage of electric line |
|||
|
+/- 25 kV |
3 000 |
3 000 |
900 |
|
+/- 85 kV |
3 000 |
3 000 |
2 100 |
3.7.6 Part 6 – exclusion zones for high voltage overhead insulated electric line for authorised and instructed persons and for operating plant and vehicles operated by authorised or instructed persons
|
Nominal phase to phase voltage of high voltage overhead insulated electric line |
Authorised person or instructed person for electric line (mm) |
Operating plant operated by authorised person or instructed person for the electric line, with safety observer or another safe system of work (mm) |
Vehicle operated by authorised person or instructed person for electric line (mm) |
|---|---|---|---|
|
Above low voltage, up to 33 kV (with consultation with person in control of electric line) |
700 |
700 |
700 |
|
Above low voltage, up to 33 kV (without consultation with person in control of electric line) |
700 |
700 |
700 |
|
Above 33 kV up to 50 kV |
750 |
750 |
750 |
|
Above 50 kV up to 66 kV |
1 000 |
1 000 |
1 000 |
|
Nominal pole to earth dc voltage of electric line |
|||
|
+/- 25 kV |
700 |
700 |
700 |
|
+/- 85 kV |
1 000 |
1 000 |
1 000 |
Last updated July 16, 2009