Access keys | Skip to primary navigation | Skip to secondary navigation | Skip to content | Skip to footer |
Office of Fair and Safe Work Queensland
Department of Justice and Attorney-General
Home > Electrical Safety > Law and penalties > Code of Practice for Electrical Work > 6. Working live > 6.5 Testing and fault-finding

6.5 Testing and fault-finding

6.5.1 General
6.5.2 Ensuring correct connections

6.5.1 General

When fault finding, testing, applying a potentially fatal test current19, or a combination of these, the common electrical hazards are likely to be present (refer to section 4.4). Consult section B.1 for information on the sources of these hazards. To control risks of this kind, a safe system of live work as outlined in section 6.3 must be in place.

Where a recognised test cannot or does not satisfactorily determine that parts are electrically safe – including proving that all connections are correct (including polarity) – or where any doubt exists, the following should apply:

To ensure electrical safety, procedures for fault finding and testing should also address:

If the procedure includes a requirement for inspections, the criteria for the inspections should be clearly identified.

Where more than one electrical worker is involved in the process of installing, testing, energising, disconnecting and rectifying, an employer or self-employed person should ensure that an electrical worker is assigned to ensuring electrical safety is maintained at all times.

An employer or self employed person should make sure a person is clearly responsible for the overall integrity of the electrical work and testing.

Electrical workers should be regularly trained and assessed in the underpinning knowledge and practical aspects of testing across the range of variables the worker will encounter.

Clear guidelines should be provided on which tester, or combination of test instruments and equipment, to use including accessories such as trailing earth leads.

6.5.2 Ensuring correct connections (including polarity)

6.5.2.1 Importance of testing for correct connections (including polarity)

Failure to ensure correct connections (including polarity) can cause serious incidents and may result in severe and even fatal injuries. Examples of hazardous situations resulting from incorrect connections (including polarity) include:

When an active and neutral are transposed in a Multiple Earthed Neutral (MEN) system, the earthed metal work, such as taps, become live, i.e. there is a significant potential to earth. An error of this kind will usually mean the supply cannot be isolated to an installation via the main switch. In this instance, the problem arises because the main switch is in the neutral and at least one active is not switched.

Connections must be tested to confirm that they are correct. The tests must be performed when any new work is energised. The same applies to any alterations or additions, or both. Testing to prove correct connections (including polarity) greatly reduces the risk of death or severe injury associated with incorrect connections (including polarity).

Using the correct test procedures will ensure the electrical work is safe and will protect the worker, other workers and the public during and after testing.

6.5.2.2 Situations when testing correct connections (including polarity) are required

Examples of when tests of correct connections (including polarity) are required include when:

6.5.2.3 Procedure for ensuring correct connections (including polarity)

Test procedures should be properly documented and effectively communicated to the appropriate persons.

The minimum steps should include proving the correct electrical relationship exists between the:

Both the source of supply and the electrical work may require testing. For example, if a three-phase generator is to supply an installation, the source – in this instance, the generator – and the installation require testing because incorrect connection/s may exist at either or both locations.

The electrical worker responsible for ensuring correct connections (including polarity) must be competent in confirming connections are correct.

6.5.2.4 Precautions when testing for correct connections (including polarity)

It is not acceptable to rely on equipment function as a means of testing connections. Examples of unacceptable test methods include:

Within the test procedure, an indication should be given as to what the test is proving. The electrical worker following the procedure should be able to clearly identify exactly what he or she is testing for. For example, is the test purely a ‘polarity’ test or does it include other measures such as proving that there is no alternative source of supply?

Installations should not be connected to de-engergised low voltage sources. The installation earthing system should not be used for tests to earth unless the insulation between the neutral and earthing system has been proven acceptable. An independent earth may be used. The installation earthing should not be used because, as the test is performed, the potential of the earthing system may rise to a level that causes an electrical hazard. In this situation, the impedance of the testing device directly affects the level of potential rise.

19 The term "potentially fatal test current" is defined in Appendix A.
20 The term "disconnected" is defined in Appendix A.

Last updated July 16, 2009