8.6 Particular circumstances

Despite the earlier provisions-where plant or equipment consists of a vehicle, possibly including an attached trailer-the plant or equipment may be driven under an overhead electric line while in transport mode only under the following circumstances:

Nominal phase to phase voltage (kV) (Exposed unless otherwise specified)

Operation of vehicle by untrained person (mm)

 

Operation of vehicle by authorised person and instructed person (mm)

Insulated low voltage with consultation & Insulation verified by AP

300

No contact

Low voltage (LV) with consultation

600

600

Low voltage (LV) without consultation

> LV & up to 33 with consultation

900

700

> LV & up to 33 without consultation

> 33 & up to 50

2100

 

 

750

> 50 & up to 66

1000

> 66 & up to 110

> 110 & up to 132

1200

> 132 & up to 220

2900

 

1800

> 220 & up to 275

2300

> 275 & up to 330

3400

3000

> 330 & up to 400

4400

 

3300

> 400 & up to 500

3900

Table 8.1 – Exclusion Zones for operation of vehicles (extract from Appendix B)