Control strategies for the presence of Legionella
This strategy is drawn from AS/NZS 3666.3 Air-handling and water systems of buildings - Microbial control - Performance-based maintenance of cooling water systems and provides an approach to dealing with the presence of Legionella in the recirculating waters of cooling towers.
|
Control strategies for the presence of legionellae |
|
Test result (cfu/mL) |
Required control strategy |
|
Not detected (< 10) |
(1) Maintain monthly or at least three monthly monitoring Maintain water treatment program. |
|
Detected as < 1000 |
(2) Investigate problem Review water treatment program. Take necessary remedial action (including immediate online disinfection). Undertake control strategy (3). |
|
(3) Retest water within 3 to 7 days of plant operation
- If not detected, continue to retest water every 3 to 7 days until 2 consecutive samples return readings of 'not detected', then repeat control strategy (1).
- If detected at < 100 cfu/mL. repeat control strategy (2).
- If detected at > 100 cfu/mL, investigate the problem and review water treatment program, and immediately carry out online decontamination.
- If detected at > 1000 cfu/mL, undertake control strategy (4).
|
|
Detected as > 1000 |
(4) Investigate problem
Review water treatment program.
Take necessary remedial action (including immediate online decontamination) and undertake control strategy (5). |
|
(5) Retest water within 3 to 7 days of plant operation
- If not detected, continue to retest water every 3 to 7 days until 2 consecutive samples return readings of 'not detected', then repeat control strategy (1).
- If detected at < 100 cfu/mL, repeat control strategy (2).
- If detected at > 100 and < 1000 cfu/mL, investigate the problem and review water treatment program, immediately carry out online decontamination), and repeat control strategy (5).
- If detected at > 1000 cfu/mL, investigate and review the water treatment program, immediately carry out system decontamination, and repeat control strategy (5).
|